125
Lutron® integration protocol
Maestro® Fan Speed Control (continued)
OUTPUT Commands
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 Levels:
0 = Off
1– 25% = Low
26 –50% = Medium
56 –75% = Medium High
76 –100% = High
Example OUTPUT Commands
Examples presume dimmer has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set fan speed to Medium High. #OUTPUT,1,1,75<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
3
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to High. ~OUTPUT,1,1,100.00<CR><LF>
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
, 1, Action Number, Parameters
LUTRON
NOTE
1. Supported only in HomeWorks® QS 4.0 or higher and RadioRA® 2 6.0 or higher.