103
Lutron® integration protocol
Tabletop seeTouch® Keypad (continued)
DEVICE Commands (continued)
DEVICE Command-specific fields (continued)
Component Numbers (continued):
Component Component Number Available Actions
LED 1 81 Set or Get LED state
LED 2 82 Set or Get LED state
LED 3 83 Set or Get LED state
LED 4 84 Set or Get LED state
LED 5 85 Set or Get LED state
LED 6 86 Set or Get LED state
LED 7 87 Set or Get LED state
LED 8 88 Set or Get LED state
LED 9 89 Set or Get LED state
LED 10 90 Set or Get LED state
LED 11 91 Set or Get LED state
LED 12 92 Set or Get LED state
LED 13 93 Set or Get LED state
LED 14 94 Set or Get LED state
LED 15 95 Set or Get LED state
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Set (#) or Get (?) LED State
Set is for unprogrammed LEDs only
9 0 = Off
1 = On
Example DEVICE Commands
Examples presume keypad has been assigned Integration ID 3.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 1. #DEVICE,3,1,3<CR><LF>
Turn On LED 1. #DEVICE,3,81,9,1<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the state of LED 1? ?DEVICE,3,81,9<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
LED 1 is On. ~DEVICE,3,81,9,1<CR><LF>