Programming
26
ViewStat Color Communicating Thermostat
AxLink Channels (Cont.)
Channel Type Function Description
149 CMD Decrement Humidify Set
Point
Continue to decrement the humidify set point
while the channel is active, ON, as if the
decrement button were being pushed.
150 CMD Increment Dehumidify Set
Point
Continue to increment the dehumidify set
point while the channel is active, ON, as if
the increment button were being pushed.
151 CMD Decrement Dehumidify Set
Point
Continue to decrement the dehumidify set
point while the channel is active, ON, as if
the decrement button were being pushed.
152-208 Not Used
209 CMD Fan Speed Low Set the Fan Speed to Low when the channel
is ON.
210 CMD Fan Speed Medium Set the Fan Speed to Medium when the
channel is ON.
211 CMD Fan Speed High Set the Fan Speed to High when the channel
is ON.
212 CMD/FDBK Lock Out State Source ? Master: Set the Lock Out Mode
: TStat: FDBK, Lock Out Mode
Changed
Channel ON: Lock Out Mode Enabled,
Channel OFF: Lock Out Mode Disabled.
213 Not Used
214 CMD Fan State On Set the Fan state to On while the channel is
ON.
215 CMD Fan State Auto Set the Fan state to Auto while the channel
is ON.
216 FDBK Fan Status Feedback, Fan Status changed, Fan status
is controlled by the TSTAT.
Channel ON: Fan is On,
Channel OFF: Fan is Off.
217-218 Not Used
219 CMD HVAC State Auto Set the HVAC state to auto while the channel
is active, ON.
220 CMD HVAC State Cool Set the HVAC state to cool while the channel
is active, ON.
221 CMD HVAC State Heat Set the HVAC state to heat while the channel
is active, ON.
222 CMD HVAC State Off Set the HVAC state to off while the channel
is active, ON.
223 CMD HVAC State Emergency
Heat
Set the HVAC state to Emergency Heat
while the channel is active, ON.
224 FDBK HVAC Cool Status Feedback, HVAC Cool Status changed
Channel ON: A/C is On,
Channel OFF: A/C is Off.
225 FDBK HVAC Heat Status Feedback, HVAC Heat Status changed
Channel ON: Heat is On,
Channel OFF: Heat is Off.
226 Not Used